2026 NEC Load Calculations | Article 220 -> Article 120
NEC Article 120 load calculations explained (2026 vs. 2023)
In the 2026 NEC, branch-circuit, feeder, and service load calculations moved out of Article 220 into Article 120. Candidates using 2023 memory rules commonly misapply 3 VA/sq ft to feeder general lighting or 10 kVA to optional dwelling tiers.
The 120.41 vs. 120.13 trap in 2026 NEC dwelling calcs
Do not confuse branch-circuit minimum sizing with feeder and service demand. Under 2026 NEC 120.41, dwelling standard general lighting feeder/service calculations drop to 2 VA per square foot, while minimum branch-circuit sizing under 120.13 stays 3 VA per square foot.
- Standard feeder/service general lighting (120.41)2 VA / sq ft
- Minimum branch-circuit lighting/receptacles (120.13)3 VA / sq ft
- Dwelling optional calculation first block (120.82(B))8,000 VA @ 100% + 40% remainder
- Noncoincident loads rule120.60 (was 220.60)
- Household electric range demand tableTable 120.55 (was Table 220.55)
Dwelling optional method: 8 kVA vs. 10 kVA
In 2023 NEC 220.82(B), you took 100% of the first 10,000 VA of general loads plus 40% of the remainder before adding HVAC. Under 2026 NEC 120.82(B), that 100% first block decreases to 8,000 VA, changing your total service VA by 1,200 VA on a standard residential service.
Frequently asked exam questions
Did 2026 NEC Article 120 replace Article 220 completely?
Yes. Load calculation rules previously organized under Article 220 in the 2023 NEC are relocated to Article 120 in the 2026 NEC.
When do I use 2 VA/sq ft versus 3 VA/sq ft in the 2026 NEC?
Use 2 VA/sq ft under 120.41 for dwelling general lighting feeder and service load calculations, and 3 VA/sq ft under 120.13 for minimum branch-circuit sizing.
How does Table 120.55 differ from Table 220.55?
Table 120.55 carries the household electric range demand columns forward into Article 120. Always inspect Column C vs. nameplate rating and Note 1 additions.